MAIN FEATURES
◆Two groups of independent PV array input andoutput for flexible application in different connection schemes;
◆Multiple PV input arrays each of which has a maximum current of 16A;
◆A high voltage fuse provided for the counterattack prevention of each PV input array;
◆A special high-voltage lightning protection device for the PV module;
◆A special high-voltage circuit breaker for output control of the PV module;
◆A degree of protection of IP65 for meeting the need of outdoor installation
| Product Specifications |
| Model | H4T | H4T2 | H6T | H8T | H10T |
| Input Data | Number Of PV Input Arrays | 4 | 4 | 6 | 8 | 10 |
| Maximum Current Of Each PV Input Array | 16A |
| Fuse For Each PV Input Array | 16A |
| Wire Number Of Each PV Input Array | PG7、4mm2 |
| Output Data | Number Of Output Channel | 1 | 2 |
| Maximum Output Current | 60A | 30A/each way, total 60A | 30A/each way, total 60A | 40A/each way, total 80A | 50A/each way, total 1 00A |
| Wire Number Of Each Output Channel | PG16, each way 8mm2 | Pg16, each way 8mm2 | Pg16, each way 10mm2 | Pg16、each way 10mm2 | Pg16、each way 12mm2 |
| Maximum Output Voltage | 440VDC |
| DC Output Circuit Breaker | Yes |
| Other Data | Protection | IP65 |
| Temperature | -30°C 〜+60°C |
| Reference Weight (net weight/gross weight) | 5.3/9.3 | 8.4/12.9 | 9.5/14.3 | 10.8/15.6 |
| Equipment Dimensions(DXWXH) | 340*300*140mm | 360*340*145mm | 400*420*145mm |
| Packing Dimensions(DXWXH) | 450*420*245mm | 470*450*255mm | 530*510*255mm |
| Cooling Method | Natural Cooling |
| Surge Protection | Yes |
| Ground Wire Number | >6mm2 |